Waste Incinerator Dioxin Control and Emission Standards|第 6 條|大氣環境|Regulation|In Force
環境部|v1.0
Last Amended: 2003-08-20
The concentrations of dioxin pollutants in stack emissions shall be calculated based on non-diluted dry emission volumes at a temperature of 273K and a pressure of 1 atmosphere. Moreover, a 10% emission oxygen concentration shall serve as the reference standard. The correction formula is as follows: 21-11 C=───.Cs 21-Os When the oxygen concentration of air introduced into an oxygen-enriched combustion system exceeds 21%, an oxygen concentration of 11% shall serve as the reference standard for its emissions. The correction formula is as follows: E-11 C=───.Cs E-Os If the values in the foregoing two paragraphs (21-Os) or (E-Os) are less than 1 they shall be calculated as 1.